EnergyMate Specifications (cont'd)
 

C. Cable Television / Telephone
1. The Power Outlet Box shall be capable of providing single cable television and telephone service through standard marine receptacles.
2. Services must be weather protected and lockable with the same requirements as B.4.
3. Low voltage wiring for television / telephone service must be continuously separated from power wiring by a non-metallic barrier.

D. Lighting
1. The Power Outlet Box shall have diffused downward directed lighting using incandescent lamps. Maximum wattage for lamps is 15w. A suitable fuse must protect each Power Outlet Box light circuit.
2. Lighting may be controlled for a group of Power Outlet Boxes from a single externally controlled source.
3. Optionally each Power Outlet Box light shall be controlled from a photocell incorporated in the Box.
4. Lighting circuit components must be accessible for maintenance with a tool to open mechanism that is both quick and easy.

E. Wiring
1. The Power Outlet Box shall be factory pre-wired of stranded copper wire and shall provide physical isolation between high and low voltage systems.
2. Access to line feed and termination areas shall be open and unobstructed. It must be convenient to hold incoming feed lines with both hands to position the ends into the lugs or posts.
3. The factory pre-wire must be adequate to supply the maximum future load according to the specific Power Outlet Box specification.